Model |
HE-040/220 |
HE-070/220 |
Outdoor Unit Tonnage |
10.5 kW (3 Ton) |
17 kW (5 Ton) |
Part Number |
50180400003 |
50180400005 |
Capacity Data |
Nominal Cooling Capacity |
10.4kW (35,500 BTU) |
16.8kW (57,300 BTU)
|
Operational Range (Cooling) |
2.6-10.5kW (9,000-36,000 BTU) |
4.4-17.6kW (15,000-60,000 BTU)
|
Nominal Heating Capacity |
11.2kW (38,200 BTU) |
17.7kW (60,400 BTU)
|
Operational Range (Heating) |
3.5 -13.9kW (11,800-47,400 BTU) |
5.5-22kW (18,700-75,000 BTU)
|
Highest Variable Airflow (l/S) |
849 l/s (1,800 CFM) |
1,038 l/s (2,200 CFM)
|
Lowest Variable Airflow |
189 l/s (400 CFM) |
189 l/s (400 CFM)
|
Power Supply |
220 Volts-1Phase-50/60 Hz |
220 Volts-1Phase-50/60 Hz
|
Nom. Full Load Amps |
22 |
30
|
Min. Circuit Size (Amps) |
35 |
36
|
Electrical Input Cooling (kW) |
3.25 |
5.3
|
Electrical Input Heating (kW) |
3.15 |
5.2
|
ACOP |
3.5 |
3.38
|
SEER |
Up to 18 |
Up to 18
|
Sound Pressure(dB)(A)@1m |
62 |
63
|
Soft Starter |
Variable Frequency |
Variable Frequency
|
Length |
96.5 cm (38") |
95.3 cm (37.5")
|
Width |
41 cm (16.14") |
41.3 cm (16.25")
|
Height |
81.3 cm (32") |
133.4 cm (52.5")
|
Weight |
70.3 kg (155 lbs) |
122 kg (269 lbs)
|
|